英文摘要
|
This study was built the relevant equipment accordance with ASTM E2307-15b, and makes appropriate adjustments with reference NFPA 285 to testing the fire resistance of calibration wall or curtain wall. The results of temperature rise curve for the test room and calibration wall surface were accords the standard of ASTM E2307-15b with the number 8 test, but the number 2 point of the temperature of the calibration wall surface will be higher than the standard of ASTM E2307-15b. This phenomenon is caused by the different flame temperature distribution on the calibration wall surface due to the different fuel nature. The design of type A, the main materials are aluminum extrusion, glass, interlayer plug, galvanized steel sheet, etc.; interlayer plugs are mainly rock wool and smoke retardant. The overall test results show that the aluminum material will be fusions by the flame. At 52min 27s, the temperature on the center region of the perimeter joint exceeds the regulation of ASTM E2307-15b, so it is judged that the fireproof and heat-blocking properties of the perimeter joint fail at this time, but the type A curtain wall is passed the regulation of NFPA 285 with the test time of 30min. The design of type B, the main materials are aluminum extrusion, steel extrusion, glass, interlayer plug, galvanized steel sheet, etc.; interlayer plugs are mainly rock wool and smoke retardant. The overall 2hr test results show that the curtain wall and the galvanized steel plate were well fixed, and no flame spread to the observation room. However, due to the quality of the construction, the thermal resistance of the perimeter joint was less than 60 minutes. The design of the type B curtain wall passed the requirements of the NFPA 285 in the 30mint test. The results were shown the materials and design methods of curtain wall have an influence on fire resistance design of type A and type B. If the fire resistance design method of the curtain wall is damaged during the test, the fireproof and anti-thermal property of the perimeter Joint will be invalid.
|
参考文献
|
-
建築技術規則-營建署(2019)。建築技術規則設計施工編第79-3 條。取自http://w3.cpami.gov.tw/law/law/lawe-2/b-rule.htm。Building Technical Regulations (2019). Design and Construction, Article 79-3. Retrieved from http://w3.cpami.gov.tw/law/law/lawe-2/b-rule.htm.
連結:
-
International Building Code (2018). 2018 International Building Code. Retrieved from https://codes.iccsafe.org/content/IBC2018?site_type=public.
-
(2006)。CNS 14281 A3381 (2006)。帷幕牆及其附屬門、窗與天窗靜態層間變位性能試驗法。中華民國國家標準。CNS 14281 A3381 (2006). Method of Test For Evaluating Performance of Curtain Walls and Skylights Due to Static Displacements Associated with Seismic Movements and Building Sway. Chinese National Standards.。
-
(2006)。CNS 13973 A3368 (2006)。帷幕牆及其附屬門、窗與天窗動態水密性性能試驗法。中華民國國家標準。CNS 13973 A3368 (2006). Method of Test for Water Penetration Performance of Building Curtain Walls and Skylights-By Dynamic Pressure. Chinese National Standards.。
-
(2015).ASTM E2307-15b (2015). Standard Test Method for Determining Fire Resistance of Perimeter Fire Barriers Using Intermediate-Scale, Multi-story Test Apparatus. ASTM International..
-
(2006)。CNS 13971 A3366(2006)。帷幕牆及其附屬門、窗與天窗氣密性性能試驗法。中華民國國家標準。CNS 13971 A3366 (2006). Method of Test for Air Permeability Performance of Building Curtain Walls and Skylights. Chinese National Standards.。
-
(2006)。CNS 13974 A3369 (2006)。帷幕牆及其附屬門、窗與天窗靜態水密性性能試驗法。中華民國國家標準。CNS 13974 A3369 (2006). Method of Test For Water Penetration Performance of Building Curtain Walls and Skylights-By Static Pressure. Chinese National Standards.。
-
(2006)。CNS 13972 A3367 (2006)。帷幕牆及其附屬門、窗與天窗正負風壓結構性性能試驗法。中華民國國家標準。CNS 13972 A3367 (2006). Method of Test for Deformation Under Wind Pressure of Building Curtain Walls and Skylights. Chinese National Standards.。
-
(2012).NFPA 285 (2012). Standard Method of Test for the Evaluation of Flammability Characteristics of Exterior Non-Load-Bearing Wall Assemblies Containing Combustible Components Using the Intermediate-Scale, Multistory Test Apparatus. National Fire Protection Association..
-
An, W,Pan, R,Meng, Q.,Zhu, H.(2018).Experimental study on downward flame spread characteristics under the influence of parallel curtain wall.Applied Thermal Engineering,128,297-305.
-
Cuzzillo, B. R.,Pagni, P. J.(1998).Thermal breakage of double-pane glazing by fire.Journal of Fire Protection Engineering,9(1),1-11.
-
International Firestop Council (2004). Perimeter Curtain Wall Fire Protection. Retrieved from https://www.firestop.org.
-
Meng, Q,Zhu, G,Yu, M.,Liang, Z.(2018).Experimental study on upward flame spread characteristics of external thermal insulation material under the influence of porosity.Case Studies in Thermal Engineering,12,365-373.
-
Shriver, J. (2009). Perimeter Fire Containment-The Basics. Retrieved from https://www.thermafiber.com/wp-content/uploads/2013/11/perimeter%20fire%20containment%20the%20basics.pdf.
-
Thermafiber, Inc. (2009). Perimeter Fire Containment in Multi-Story Buildings. Retrieved from https://www.thermafiber.com.
-
Yu, M,Zhu, G.,Meng, Q.(2018).Experimental study and analysis of xps vertical countercurrent fire spread.Procedia Engineering,211,945-953.
-
Zhou, L,Chen, A,Gao, L.,Pei, Z.(2017).Effectiveness of vertical barriers in preventing lateral flame spread over exposed EPS insulation wall.Fire Safety Journal,91,155-164.
-
台灣中油股份有限公司(2015)。LNG 及LPG 之差異。取自https://new.cpc.com.tw/division/lngb/information-text.aspx?ID=33。CPC Corporation, Taiwan (2015). Difference between LNG and LPG. Retrieved from https://new.cpc.com.tw/division/lngb/information-text.aspx?ID=33。
-
李書彰(2011)。台南市=Tainan City,崑山科技大學機械工程研究所=Department of mechanical engineering, Kun Shan university。
-
李錦堃(2011)。新北市=New Taipei City,東南科技大學防災科技研究所=Department of disaster prevention science and technology, Tungnan University。
-
許燕輝(2005)。新竹市=Hsinchu City,國立交通大學工學院營建技術與管理研究所=Construction Technology and Management College of Engineering, National Chiao Tung university。
-
陳太農、郭炳林(1999)。內政部建築研究所研究報告內政部建築研究所研究報告,新北市=New Taipei City:內政部建築研究所=Architecture and Building Research Institute, Ministry of the Interior, ROC (Taiwan)。
-
陳宗熙(1991)。新北市=New Taipei City,淡江大學建築學系=Department of Architecture, Tamkang University。
-
陳慶銘、王榮吉、施乃中(1992)。內政部建築研究所研究報告內政部建築研究所研究報告,新北市=New Taipei City:內政部建築研究所=Architecture and Building Research Institute, Ministry of the Interior, ROC (Taiwan)。
-
蕭江碧、劉慶男、何明錦(2002)。內政部建築研究所研究報告內政部建築研究所研究報告,新北市=New Taipei City:內政部建築研究所=Architecture and Building Research Institute, Ministry of the Interior, ROC (Taiwan)。
|