题名

以鋼索補強之牙桿懸吊管線系統耐震補強研究

并列篇名

A Study on Cable Restrained Seismic Behavior of Suspended Piping Systems with Rod Support

DOI

10.53106/101632122023060124006

作者

柯敏琪(Min-Chi Ko);姚昭智(George C. Yao)

关键词

設備物系統 ; 懸吊式消防撒水系統 ; 共同管線吊架 ; 鋼索補強 ; 牙桿懸吊 ; Non-Structure Components ; Suspended Fire-Protection Sprinkler Piping System ; Suspended Piping Trapeze System ; Cable Restraint Components ; Rod Support

期刊名称

建築學報

卷期/出版年月

124期(2023 / 06 / 30)

页次

101 - 116

内容语文

繁體中文;英文

中文摘要

台灣在公共工程、醫院等建築物中,經常以螺紋牙桿為懸吊構件,支撐裝載水系的單桿管線或共同吊架,例如:懸吊式消防撒水系統、懸吊式共同管線吊架系統等。然而,多數的懸吊設備不會額外顧及受震振動問題,僅考慮自重支撐是否足夠,因此該類型以螺紋牙桿為懸吊構件的設備,經常在地震中震動過大損壞、漏水,造成使用空間既有機能停擺、增加維修成本。本研究針對國內常見螺紋牙桿之消防撒水系統與共同管線吊架系統,及其常用之施工與補強方式,參考NFPA13與ISAT之補強建議下,利用經UL認證市售鋼索補強,進行振動台實驗,分析比較補強前後系統識別、動靜態特性差異。實驗顯示利用鋼索補強可以大量降低地震造成的管線振動量,確認該補強構件為實務亦可使用之耐震補強策略。

英文摘要

In Taiwan, rod supports are usually used for suspension systems in hospitals and public spaces,such as fire-sprinkler piping systems and trapeze systems. Because pipe breakage and leakage after an earthquake can reduce the building function and cost lots of money and time to recover, the dynamic behavior of the above systems is important to understand before a good retrofit program is proposed. This study focuses on the rod support for suspended fire-protection sprinkler piping systems and suspended trapeze system. Retrofitted with cables that satisfied the seismic component requirements from NFPA13 and ISAT, and the cable restraint components which were certified by UL, we studied their dynamic behavior. By shaking table tests, the system identification and system characteristic were analyzed for before and after retrofit. Test results indicated that cables are effective to reduce the horizontal displacement of rod supported piping and trapeze systems in earthquake motion.

主题分类 工程學 > 土木與建築工程
参考文献
  1. America Society for Testing and Materials(2011).America Society for Testing and Materials (2011). ASTME580/E580M-11ae1: Standard Practice for Installation of Ceiling Suspension Systems for Acoustical Tile and Lay-in Panels in Areas Subject to Earthquake Ground Motions. ASTM E580/E580M-11ae1, West Conshohocken, PA..
  2. American Society of Civil Engineers(2010).ASCE 7-10: Minimum Design Loads for Buildings and Other Structures.Reston, VA.:
  3. Federal Emergency Management Agency(2007).FEMA461: Interim Testing Protocols for Determining the Seismic Performance Characteristic of Structure and Nonstructural Components.USA:Federal Emergency Management Agency.
  4. Huang, B.,Lu, W.,Mosalam, K. M.(2017).Shaking table tests of the cable tray system in nuclear power plants.Journal of Performance of Constructed Facilities,31(4),04017018.
  5. ICC Evaluation Service inc(2007).ICC Evaluation Service inc. (2007). AC156: Acceptance Criteria for Seismic Qualification by Shake-table Testing of Nonstructural Components and Systems. AC156, ICC-ES..
  6. International Seismic Application Technology(2002).Engineered Seismic Bracing of Suspended Utilities.USA:ISAT.
  7. Ko, M. C.,Yao, George C.,Nagae, T.,Chung, Y. L.,Chen, W. C.(2020).A study on suspended fire protection sprinkler piping systems in buildings.17th World Conference on Earthquake Engineering 2020,Sendai, Japan:
  8. Loos, Co(2001).Manual of Code Compliance Guidelines.USA:
  9. National Fire Protection Association(2010).NFPA13: Standard for the Installation of Sprinkler.Massachusetts, USA:NFPA.
  10. Perrone, D.,Brunesi, E.,Filiatrault, A.,Peloso, S.,Nascimbene, R.,Beiter, C.,Piccinin, R.(2020).Seismic numerical modelling of suspended piping trapeze restraint installations based on component testing.Bulletin of Earthquake Engineering,18(4),1499-1524.
  11. Perrone, D.,Filiatrault, A.,Peloso, S.,Brunesi, E.,Beiter, C.,Piccinin, R.(2020).Experimental seismic response evaluation of suspended piping restraint installations.Bulletin of Earthquake Engineering,18(4),1499-1524.
  12. Soroushian, S.,Maragakis, E. M.,Ryan, K. L.,Sato, E.,Sasaki, T.,Okazaki, T.,Mosqueda, G.(2016).Seismic simulation of an integrated ceiling-partition wall-piping system at E-defense. II: Evaluation of nonstructural damage and fragilities.Journal of Structural Engineering,142(2),04015131.
  13. The Office of Statewide Health Planning and Development(2011).California Senate Health Committee Hearing on Hospital Seismic Safety.CA:OSHPD.
  14. Tian, Y.,Filiatrault, A.,Mosqueda, G.(2015).Seismic response of pressurized fire sprinkler piping systems II: Numerical study.Journal of Earthquake Engineering,19(4),674-699.
  15. Tian, Y.,Filiatrault, A.,Mosqueda, G.(2015).Seismic response of pressurized fire sprinkler piping systems I: Experimental study.Journal of Earthquake Engineering,19(4),649-673.
  16. Underwriter Laboratories Inc(2015).UL203A:Standard for Sway Brace Devices for Sprinkler System Piping.Illinois, USA:UL.
  17. Zaghi, A. E.,Maragakis, E. M.,Itani, A.,Goodwin, E.(2011).Experimental and Analytical Studies of Hospital Piping Assemblies Subjected to Seismic Loading.Structure Congress
  18. 王仁佐, R. T.,王修賢, H. H.(2018)。,台北=Taipei, Taiwan:財團法人國家實驗研究院國家地震工程研究中心=National Center for Research on Earthquake Engineering。
  19. 王仁佐, R. T.,沈文成, W. C.(2013)。,台北=Taipei, Taiwan:財團法人國家實驗研究院國家地震工程研究中心=National Center for Research on Earthquake Engineering。
  20. 行政院公共工程委員會(2013)。施工綱要規範:第15060 章吊掛及支撐。行政院公共工程委員會,台北市。Public Construction Commission, Executive Yuan (2013). Implementation Guidelines for the Outline Specifications for Public Construction Chapter 15060, Hangers and Supports. Public Construction Commission, Executive Yuan, Taipei, Taiwan. Available online: https://pcces.pcc.gov.tw/csi/Default.aspx?FunID=Fun_9_3&SearchType=B
  21. 宋裕祺, Y. C.,李昭賢, C. H.(2010)。,台北=Taipei, Taiwan:財團法人國家實驗研究院國家地震工程研究中心=National Center for Research on Earthquake Engineering。