The Effect of Doorway Size on the Negative Pressure in Airborne Infection Isolation Room

DOI

10.7005/JOSH.201009.0307

作者

TH Tsao;Cheng-Ping Chang;Chi-Yu Chuang;Yow-Jer Juang;Sheng-Jie Lin;Yu-Tung Dai

关键词

Airborne infection isolation room ; Air change per hour ; Negative pressure

期刊名称

勞工安全衛生研究季刊

卷期/出版年月

18卷3期(2010 / 09 / 01)

页次

307 - 319

内容语文

英文

英文摘要

The location of air supply and exhaust, differential of supply and exhaust air, air change per hour and negative pressure have been proposed in the specification of negative pressured isolation ward. The purpose of negative pressure is to prevent virus from spreading out. The doorway size is an important factor on negative pressure. However, the doorway size is never suggested in the guidelines. The aim of this study is to investigate the effect of doorway size on pressure difference under different room sizes and air change rates. A volume adjustable chamber with independent ventilation system was used to simulate negative pressured isolation room without anteroom. By changing doorway size, the corresponding negative pressure could be measured under different room size and air change per hour (ACH). It was found that the negative pressure decreases with the increasing doorway size, and reaches to zero when the doorway size is large enough. When the doorway size is fixed, the pressure difference decreases with ACH. When the ACH is equal to 4, the pressure difference is always smaller than 8 Pa though the doorway size is kept at minimum (0.2cm). Therefore, to maintain negative pressure is equal to 8 Pa, the ACH is required to be greater than 4, or increasing the exhaust air at least 20% greater than supply air. The model of doorway size was also developed by using the experimental data. The results provide useful information for future design and improvement of negative pressured isolation ward.

主题分类 醫藥衛生 > 預防保健與衛生學
醫藥衛生 > 社會醫學
社會科學 > 社會學