题名

智慧溫感外牆之隔熱應用研究

并列篇名

Application of Smart Temperature-Controlling Building Envelope for Thermal Insulation

作者

張智元(Chih-Yuan Chang);易永秋(Yung-Chiu Yi);李昀修(Yun-Siou Lee)

关键词

智慧外牆 ; 電熱晶片 ; 溫控外牆 ; 建築延壽 ; 智慧建築 ; Smart skin ; thermal electrical chip ; controllable building envelope ; building life extension ; smart building

期刊名称

物業管理學報

卷期/出版年月

8卷2期(2017 / 09 / 30)

页次

31 - 40

内容语文

繁體中文

中文摘要

臺灣目前大部分的建築結構體材料為鋼筋混凝土,但鋼筋混凝土有高蓄熱及熱導性,使建物在面臨日益嚴峻的外部熱環境時,維持舒適的溫控環境日益困難,除了造成額外能源消耗,亦對特定使用者身體健康造成威脅,更因溫差頻繁導致混凝土結構收縮,對結構體壽命造成不良影響。本研究將電熱晶片導入智慧溫控外牆,透過預埋入外牆之銅管溫控模組及智慧溫感建材,來執行智慧間歇性反趨點對流模式判斷,藉此讓溫控調節器對牆體進行溫度控制。經實驗後證實智慧間歇性反趨點對流模式為較佳的供應時域及換氣頻率模式,若使用此模式可增加熱交換時間,相較瞬時熱交換情境可增加一倍的降溫效果,目前在致冷溫控最佳可控制牆體降溫2℃的效果。

英文摘要

Most buildings in Taiwan were built with reinforced concrete, a material with high heat storage capacity and thermal conductivity. In the face of an increasingly severe external thermal environment, sustaining a comfortable temperature-controlled environment in these buildings has become increasingly difficult, which not only leads to extra energy consumption and health risk to specific users, but also causes reinforced concrete structures to contract because of frequent temperature variations, thereby exerting an adverse influence on their structural life. In this study, thermal electrical chips were incorporated into smart temperature-controlling building envelope. Copper tube temperature-controlling modules and smart temperature information materials that were pre-embedded in the building envelope were employed to calculate the timing for implementing the smart intermittent inflection point convention model, thus enabling temperature adaptive regulators to control wall temperatures. Experimental results verified that the smart intermittent inflection point convention model provided a relatively satisfactory supply time domain and ventilation frequency mode and could extend heat exchange time. In comparison with instantaneous heat exchange scenarios, the cooling effect of the proposed model could be doubled. The current optimal cooling effect could lower wall temperatures by 2°C.

主题分类 社會科學 > 管理學
参考文献
  1. 蘋果日報(2014)。朝5 晚8 死亡率最高時刻。取自https://goo.gl/GznTxZ
  2. Cataldo, A.,De Benedetto, E.,Cannazza, G.,Monti, G.,Piuzzi, E.(2017).TDR-based monitoring of rising damp through the embedding of wire-like sensing elements in building structures.Measurement,98,355-360.
  3. Chang, C. Y.,Hung, S. S.,Peng, Y. F.(2011).An evaluation of the embedment of a radio frequency integrated circuit with a temperature detector in building envelopes for energy conservation.Energy and Buildings,43(10),2900-2907.
  4. Chen, S. Y.,Chiu, M. L.(2007).Designing smart skins for adaptive environments: A fuzzy logic approach to smart house design.Computer-Aided Design and Applications,4(6),751-760.
  5. Franzoni, E.,Pigino, B.,Graziani, G.,Lucchese, C.,Fregni, A.(2016).A new prefabricated external thermal insulation composite board with ceramic finishing for buildings retrofitting.Materials and Structures,49(4),1527-1542.
  6. Huang, K.,Li, B.,Yan, Y.,Li, Y.,Twaha, S.,Zhu, J.(2017).A comprehensive study on a novel concentric cylindrical thermoelectric power generation system.Applied Thermal Engineering,117,501-510.
  7. Irshad, K.,Habib, K.,Basrawi, F.,Saha, B. B.(2017).Study of a thermoelectric air duct system assisted by photovoltaic wall for space cooling in tropical climate.Energy,119,504-522.
  8. Irshad, K.,Habib, K.,Basrawi, F.,Thirumalaiswamy, N.,Saidur, R.,Saha, B. B.(2015).Thermal comfort study of a building equipped with thermoelectric air duct system for tropical climate.Applied Thermal Engineering,91,1141-1155.
  9. Irshad, K.,Habib, K.,Thirumalaiswamy, N.,Saha, B. B.(2015).Performance analysis of a thermoelectric air duct system for energy-efficient buildings.Energy,91,1009-1017.
  10. Kim, T. Y.,Negash, A. A.,Cho, G.(2016).Waste heat recovery of a diesel engine using a thermoelectric generator equipped with customized thermoelectric modules.Energy Conversion and Management,124,280-286.
  11. Krüger, E. L.(2015).Urban heat island and indoor comfort effects in social housing dwellings.Landscape Urban Planning,134,147-156.
  12. Larsen, L.,Coseo, P.(2014).How factors of land use/land cover, building configuration, and adjacent heat sources and sinks explain Urban Heat Islands in Chicago.Landscape Urban Planning,125,117-129.
  13. Loonen, R. C.,Trčka, M.,Cóstola, D.,Hensen, J. L. M.(2013).Climate adaptive building shells: State-of-the-art and future challenges.Renewable and Sustainable Energy Reviews,25,483-493.
  14. Luo, Y.,Zhang, L.,Liu, Z.,Wang, Y.,Meng, F.,Xie, L.(2016).Modeling of the surface temperature field of a thermoelectric radiant ceiling panel system.Applied Energy,162,675-686.
  15. Lv, S.,He, W.,Wang, L.,Li, G.,Ji, J.,Chen, H.,Zhang, G.(2016).Design fabrication and feasibility analysis of a thermo-electric wearable helmet.Applied Thermal Engineering,109,138-146.
  16. Magno, M.,Brunelli, D.,Sigrist, L.,Andri, R.,Cavigelli, L.,Gomez, A.,Benini, L.(2016).InfiniTime: Multi-sensor wearable bracelet with human body harvesting.Sustainable Computing: Informatics and Systems,11,38-49.
  17. Moon, J. W.,Lee, J. H.,Chang, J. D.,Kim, S.(2014).Preliminary performance tests on artificial neural network models for opening strategies of double skin envelopes in winter.Energy and Buildings,75,301-311.
  18. Moon, J. W.,Lee, J. H.,Kim, S.(2014).Application of control logic for optimum indoor thermal environment in buildings with double skin envelope systems.Energy and Buildings,85,59-71.
  19. Park, C. S.,Augenbroe, G.,Sadegh, N.,Thitisawat, M.,Messadi, T.(2003).Occupant responsive optimal control of smart facade system.Eighth international IBPSA conference,Netherlands:
  20. Rainieri, C.,Fabbrocino, G.,de Magistris, F. S.(2013).An integrated seismic monitoring system for a full-scale embedded retaining wall.Geotechnical Testing Journal,36(1),40-53.
  21. Rodrigues, C.,Freire, F.(2017).Building retrofit addressing occupancy: An integrated cost and environmental life-cycle analysis.Energy and Buildings,140,388-398.
  22. Sallée, H.,Quenard, D.,Valenti, E.,Galan, M.(2014).VIP as thermal breaker for internal insulation system.Energy and Buildings,85,631-637.
  23. Santos, P.,Martins, C.,Júlio, E.(2015).Enhancement of the thermal performance of perforated clay brick walls through the addition of industrial nano-crystalline aluminium sludge.Construction and Building Materials,101,227-238.
  24. Sheikhzadeh, G. A.,Azemati, A. A.,Khorasanizadeh, H.,Hadavand, B. S.,Saraei, A.(2014).The effect of mineral micro particle in coating on energy consumption reduction and thermal comfort in a room with a radiation cooling panel in different climates.Energy and Buildings,82,644-650.
  25. Shen, C.,Li, X.(2017).Energy saving potential of pipe-embedded building envelope utilizing low-temperature hot water in the heating season.Energy and Buildings,138,318-331.
  26. Simons, R. E.,Ellsworth, M. J.,Chu, R. C.(2005).An assessment of module cooling enhancement with thermoelectric coolers.Transactions of the ASCE-C-Journal of Heat Transfer,127(1),76-84.
  27. Su, C. Q.,Zhu, D. C.,Deng, Y. D.,Wang, Y. P.,Liu, X.(2017).Effect of cooling units on the performance of an automotive exhaust-based thermoelectric generator.Journal of Electronic Materials,46(5),2822-2831.
  28. Tam, B. Y.,Gough, W. A.,Mushin, T.(2015).The impact of urbanization and the urban heat island effect on day to day temperature variation.Urban Clime,12,1-10.
  29. Wong, J.,Li, H.,Lai, J.(2008).Evaluating the system intelligence of the intelligent building systems: Part 1: Development of key intelligent indicators and conceptual analytical framework.Automation in Construction,17(3),284-302.
  30. 李海飛、水中和、孫濤(2010)。溫度—濕度迴圈對混凝土結構和性能的影響。工程科技與教育學刊,7(2),349-353。
  31. 周振华(2003)。产业融合产业在展及经济培长的新动力。中国工業经济,4,46-52。