题名

單級磁浮離心式冷媒壓縮機容調機構之降載能力實測研究

并列篇名

Research on Turn Down Capability of Single-stage AMB Centrifugal Refrigerant Compressor with Variable Diffuser Mechanism

作者

鐘震麒(Jenn-Chyi Chung);林俊傑(Jun-Jie Lin);洪國書(Kuo-Shu Hung);劉中哲(Chung-Che Liu)

关键词

主動式磁浮軸承 ; 離心式冷媒壓縮機 ; 可變擴壓器 ; 喘震 ; 降載比例 ; Active magnetic bearing ; Centrifugal refrigerant compressor ; Variable diffuser mechanism ; Surge ; Turn down ratio

期刊名称

冷凍空調&能源科技

卷期/出版年月

119期(2020 / 01 / 10)

页次

63 - 67

内容语文

繁體中文;英文

中文摘要

本研究探討離心式冷媒壓縮機擴壓器寬度對低負載抗喘震能力之影響。以額定製冷能力240 USRT具可變寬度擴壓器之磁浮離心式冷媒壓縮機為實測體,測試其在固定冰水出水溫度與不同冷卻水入水溫度條件下,改變擴壓器寬度量測其製冷能力的變化。實測結果顯示,模擬冷卻水入水溫度30.0±0.5℃、冰水出水溫度7.0±0.5℃,在額定最高轉速18,560rpm與最小擴壓器寬度1.0mm,測得最低製冷能力為98.9USRT,降載比例為額定製冷容量的58.8%;配合調降轉速至喘震轉速16,980rpm時,則製冷能力降低至70.5USRT,降載比例為額定製冷容量的70.62%。另模擬冷卻水入水溫度19.0±0.3℃、冰水出水溫度7.0±0.3℃,維持15,080rpm的轉速條件下,最小擴壓器寬度1.0mm,所測得之最低製冷能力為88.9USRT,降載比例為額定製冷容量的62.96%;配合調降轉速至喘震轉速12,960rpm時,降載比例為額定製冷容量的86.5%。

英文摘要

This study investigated the effect of the diffuser width on surge prevention. The test object is the rated 240USRT AMB (active magnetic bearing) R134a centrifugal compressor which equipped with variable diffuser mechanism. To measure the variation of cooling capacity of different diffuser width. It's tested under certain chilled water outlet and different cooling water inlet temperature. The test results show that the lowest cooling capacity is 98.9USRT at the speed of 18,560rpm and the lowest width 1.0mm. Which the cooling water inlet temperature is 30.0±0.5℃ and the chilled water outlet temperature is 7.0±0.5℃. It is 58.8% of the rated cooling capacity. When the rotation speed is further down to the surge limit speed of 16,980rpm. The cooling capacity reduced to 70.5 USRT. The turn down ratio is 70.62% of the rated cooling capacity. If the rotation speed maintained at 15,080rpm and the lowest width 1.0mm. Which the cooling water inlet temperature is 19.0±0.3℃ and the chilled water outlet temperature is 7.0±0.3℃. The lowest cooling capacity is 88.9USRT, which is 62.96% of the rated cooling capacity. When the rotation speed is further down to the surge limit speed of 12,960rpm. The turn down ratio is 86.5% of the rated cooling capacity.

主题分类 工程學 > 電機工程
参考文献
  1. Kim, H. W.,Ryu, S. H.,Park, J. I.,Ghal, S. H.,Ha, J. S.(2006).The numerical study on the performance evaluations and flow structures for the diffuser of centrifugal compressor in a marine engine turbocharger.ASME 2006 Internal Combustion Engine Division Fall Technical Conference
  2. Koumoutsos, A.,Tourlidakis, A.,Elder, R.L.(2000).Computational studies of unsteady flows in a centrifugal compressor stage.Proceedings of the Institution of Mechanical Engineers, PaUSRT A: Journal of Power and Energy,214(6),611-633.
  3. Pampreen, Ronald C..Compressor surge and stall.Concepts ETI, Inc..
  4. Pinarbasi, A.,Johnson, M. W.(1994).Off design Reynolds stress tensor measurements in a centrifugal compressor vaneless diffuser.American Society of Mechanical Engineers, Fluids Engineering Division (Publication) FED,203,43-49.
  5. Salvage, J.W.(1999).Development of a centrifugal compressor with a variable geometry split-ring pipe diffuser.Journal of Turbomachinery,121(2),295-304.
  6. Tamaki, H.,Nakao, H.,Saito, M.(1999).The experimental study of matching between centrifugal compressor impeller and diffuser.Journal of Turbomachinery,121(1),113-118.
  7. Zhang, W.,Wang, Y.,Xu, Z.,Zhang, H.(2005).Digital PaUSRTicle Image Velocimetry (DPIV) investigation of the flow characteristics within the vaneless diffuser of a centrifugal blower.Kongqi Donglixue Xuebao/Acta Aerodynamica Sinica,23(2),144-151.
  8. 劉中哲,陳景富,洪財旺,江時昌,鐘震麒。廣域高效率離心式冰水機系統技術。冷凍空調與能源雜誌